Calculating VFD Energy Savings and Payback in Four Steps

Calculating VFD Energy Savings and Payback in Four Steps

A variable frequency drive (VFD) retrofit starts with the load type, because it decides everything else. Fans and centrifugal pumps are variable-torque loads: flow varies with speed, pressure with the square of speed and shaft power with the cube. A pump or fan running at 80% speed therefore absorbs about 51% of its rated power. Constant-torque loads such as conveyors and positive-displacement compressors scale linearly with speed, so the saving is proportionally smaller. Anyone quoting a flat 30% saving for every application is guessing.

Second, build the load duration curve. Write down how many hours per year the machine runs at each flow or pressure the process actually needs, rather than assuming it runs at rated duty. Most oversized fans and pumps are throttled or bypassed for the majority of their operating hours — that throttling is exactly where the cubic law turns into money. A realistic duration curve is worth more than a precise motor efficiency figure.

Third, convert to kWh using motor efficiency, drive losses (typically 2 to 3%) and your tariff structure, remembering to include demand charges if the utility bills peak kW. Fourth, subtract the installed cost of the drive, the harmonics mitigation you chose and any panel work, then divide by annual saving to get payback. Run the calculation at two flow profiles: an optimistic and a conservative one. If the conservative case still pays back inside your investment horizon, the project is worth approving; if only the optimistic case works, the honest recommendation is to instrument the machine for a month first and measure the real duration curve.

VFD Applications

Every variable frequency drive (VFD) application is different, because every load behaves differently. These guides explain the drive features that matter for your industry and link to the recommended product range.

All industry guides

Related product range

Low Voltage VFD

Back to news & casesAll news